info@arkasil.ch

Arkasil termination with composite type insulator is used for cable line joints with other elements of power-supply systems. Termination MKB 252 is used for outdoor and indoor installation, for XLPE cables 127/220 kV with the conductor cross section up to 2500 mm2.
Basic components
Insulator:
• composite type insulator with glass fiber reinforced epoxy resin tube and silicone rubber sheds
• sheds color–light gray
• top and bottom flanges glued and sealed to the composite insulator
Cable end:
• pre-moulded and factory-tested silicon stress cone
• cable end
• base plate
• branch pipe with flange
• support insulators
• seals and fixing materials
• unpressurised synthetic oil as an insulating compound
• optic fiber outlet

Area of application
Type МKB 252
Phase voltage                  kV                        127
Line voltage                     kV                        220
Maximum system voltage  kV                        252
Cable conductor cross
section range                  mm2                400÷2500
Maximum cable sheath
diameter                        mm                       150
Maximum cable insulation
diameter                        mm                       115

Technical data

Electrical parameters:
AC voltage withstand test                    318 kV for 30 min
Partial discharges                               <5 pC at 190 kV
Impulse voltage
(10+/10- impulses)                                   1050 kV

Climatic characteristics:
Temperature                                        -500C / +450C

Nominal operating current:
Rated operational current               limited by cable specification
Short circuit current                        limited by cable specification


Creepage distance length   mm   6190, 7636, 8058,8903, 9959, 10382

Pollution level in accordance
with IEC 60137;                                         II,III, IV
GOST 9920-89

Stress cone routine tests for MKB 252:
AC voltage withstand test                     318 kV for 30 min
Partial discharges                                <5pC at 190 kV
Cable sheath test voltage:
AC voltage 10 kV
DC voltage 20 kV

Mechanical characteristics:
Maximum allowed inclination
angle                                                        30° (45°)
Approximate weight,                  kg                  350
Maximum allowed force on
top connector,                           Н                  5000

Type tests according to IEC 62067.

 

© 2011 ARKASIL SK