GIS terminations 110 kV

Arkasil GIS terminations are used for cable lines connection to gas-insulated switchgears and transformers. MBB 126 / MBB 145 / MBB 170 are used for indoor installation for XLPE cables 64/110, 76/132 kV (conductorcross-section 185-2500 mm2).

GIS terminations could be produced for XLPE cable with optical fibers in screenwhich are used for temperature monitoring. All types of GIS terminations are made in accordance with IEC 62271-209 and could be used with switchgears for dry type and oil filled GIS terminations. GIS terminationconsists of epoxy insulator and plug-in part.

Due to such design cable if can be disconnected from the GIS andconnected again without SF6 or oil evacuation. The epoxy insulator сan be delivered with GIS (epoxy insulatorinstalled in switchgear by the manufacturer).

Marking of GIS termination MBB


Area of application   
Type МВВ 126 А (B) МВВ 145 А (B) МВВ 170 А (B)
Maximum system voltage, kV  126  145  170
Maximum cable diameter, mm 125
Cable conductor cross-section range, mm2  185÷1600 (400÷2500)
Cable insulation diameter, mm 47÷84 (55÷103)
Electrical parameters   
 AC voltage withstand test  160 kV for 30 min  190 kV for 30 min  218 kV for 30 min
 Impulse voltage (10+/10- impulses), kV  550  650  750
 Partial discharges  < 5 pC at 96 кV  < 5 pC at 114 кV  < 5 pC at 131 кV
Climatic characteristics   
Operation temperature -25 +50°С -25 +50°С -25 +50°С
Current load rating   
Rated operational current limited by cable specification
Short circuit current limited by cable specification
Stress cone routine tests   
AC voltage withstand test 160 kV for 30 min 190 kV for 30 min 218 kV for 30 min
Partial discharges <5 pC at 96 кV <5 pC at 114 кV <5 pC at 131 кV
Mechanical characteristics   
Approximate weight, kg 50 (54) 50 (54) 50 (54)
Length, mm 1200 1200 1200


 

© 2011 ARKASIL SK